Voltage detecting systems

Orion M1

With large LCD display with backlight

Technical specifications

Orion 3.1: Nominal frequency 50 or 60 Hz
Orion M1: Nominal frequency 16,7, 50, 60 Hz (adjustable)
Orion M1: Current measurement

Measuring range 1: 0 to 5 µA (±2 %)

Measuring range 2: 0 to 25 µA (±2 %)

Orion M1: Phase angle measurement

Measuring range: -180° to 180° (±1°)

Orion M1: Harmonic voltage measurement

Bar graph: 0 to 5 % / 0 - 10 %

THD: 0 - 100 % (±1 %)

Harmonic (2 - 40): 0 to 100 % (±1 %)

Indication Orion 3.1

RGB LEDs

Indication Orion M1

RGB LEDs

LCD Display

Internal power supply

4 mignon cells ; replaceable

6 years of service life, 1,000 operating cycles/year

External auxiliary supply -
CT powered -
Housing -
Temperature range -25 to +55 °C, below -15 °C LED indication only
Cable diameter -