NEW: Wega PD

Integrated voltage detecting system with innovative partial discharge monitoring

Wega PD is a 2-in-1 device that, in addition to its voltage detecting system function, performs continuous partial discharge monitoring. Wega PD monitors all connected medium- and high-voltage equipment and remotely reports critical partial discharges. Assembly and manufacturing faults as well as insulation damage caused by ageing effects are detected in good time before an unexpected fault occurs.
The 24-hour auto-learning mode for self-adjusting the partial discharge threshold value enables easy commissioning, regardless of cable type or boundary conditions at the installation site.
The integrated early fault detection enables early detection of potential fault and thus contributes significantly to increased supply reliability.

The following medium voltage conditions are displayed:

Voltage presentVoltage presentThreshold values for voltage presence indication: 0.1 — 0.45 x Vnom
Installation note: The voltage signal is too low when operating the system at nominal voltage.
The cause is usually the selected adjustment capacitor which is too large or the operation of the
switchgear at a nominal voltage that is lower than originally envisaged.
Voltage present Voltage present Voltage present and integrated maintenance test passedVoltage present and integrated maintenance test passedThe current flowing through the display unit meets the current monitoring requirements of
IEC 61243-5 and IEC 62271-213. A maintenance test is not necessary due to the continuous monitoring.
Voltage present and integrated maintenance test passed, but voltage signal too highVoltage present and integrated maintenance test passed; voltage signal, nonetheless, is too highInstallation note: Voltage signal too high. The cause is usually the selected adjustment capacitor
which is too small, an earth fault or the operation of the switchgear at a nominal voltage that is
higher than originally envisaged.
Voltage not presentVoltage not presentWhen all poles of the system are switched off, all symbols are switched off. Voltage present <0.1 x Un.

The built-in display test function on the front allows the display to be tested when installed and de-energized. Shielded or unshielded cables with compact plugs (AMP) can be connected to the fault direction indicator.

Product features

  • Online partial discharge monitoring and voltage detecting system in one Wega
  • PD warning and alarm: local display via yellow & red LED
  • Remote signaling of critical partial discharge sequences via relay
  • 15-stage PD sensitivity adjustment via rotary switch
  • Tool-free mounting and dismounting
  • Flexible C1 connection options (AMP and blade terminal)
  • Decoupled output to the short-circuit indicator (OUT)
Black, white device with LED display and two LED lamps

Integrated phase-selective voltage display

Full LRM interface (IEC 62271-213) for use with Orion 3.1 / M1

Display test button

LED: Warning and alarm levels for partial discharge activities

Your added value

  • Online partial discharge monitoring without the use of HFCTs or additional filter circuits – Quick & easy installation
  • Integrated early fault detection – increasing supply reliability
  • PD self-adjustment – simple commissioning
  • Tool-free installation – quick and easy installation
  • Integrated maintenance test – Maintenance-free
  • Fully encapsulated electronics – High functional reliability
  • -40 °C to 75 °C – Extended temperature range
  • Decoupled voltage transmission – Increased safety
Gerät mit verschiedenen Anschlüssen und Relais

Voltage input
Flat terminal

Voltage output
Compact connection

Voltage input
Compact connection

Relay contact connection for PD remote indication

Rotary switch for PD sensitivity adjustment or 24h self-adjustment

Technical data

Wega PD
Nominal voltagefrom 1 kV
Nominal frequency50 – 60 Hz
Interfaces
  • 3 LRM measuring sockets (one per phase) and 1 earth socket
  • LRM system, socket spacing 14 mm, with captive dust cap
Indication
  • LCD display with arrow, dot and tool symbols
  • LED display for warning and alarm levels for online partial discharge monitoring
Power supply
  • LCD display via measuring signal
  • Relay and LEDs via 24 DC
Auxiliary power supply24 V DC ±15 % / ripple < 100 mVpp (peak-to-peak)
PD remote indication1 relay contact, changeover contact
Input/ OutputInput: flat terminal or compact connection (AMP) | Output: compact connection (AMP)
HousingPolycarbonate, IP54
Temperature range-40 °C to +75 °C

All important documents for the device

Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.

Matching articles

PERFECT MATCH

Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.

Equipment set

  • 1 Wega PD display unit

Other integrated voltage detecting systems

Wega 1

Wega 1 V

Wega 2 integrated voltage detecting system with cover

Wega 2

Wega 2 integrated voltage detecting system with cover

Wega 2 V