Sigma R+D 2.0 | Sigma R+D 2.0 AC/DC

Combined short-circuit and earth fault indicator

The Sigma F+E 2.0 is a combined short-circuit and earth fault indicator. Due to the measuring principle, the earth fault indicator is suitable for networks with low-resistance, rigidly earthed or insulated neutral point treatment. The Sigma 2.0 series measures current via three single-phase current sensors. This enables phase-selective fault detection and display. For short-circuit excitation, you can choose between two excitation criteria – fixed response values with response delay or self-adjustment depending on the operating current. If the current of the selected response criterion – fixed response value or self-adjustment – is exceeded, the LED of the relevant phase flashes and the remote signaling contact is activated. If a second excitation occurs within the reset time, e.g. due to automatic reclosing, this is signaled by a double flashing display and the remote signalling contact is activated again. For testing and commissioning purposes, the current response values can be reduced to 10 A without changing the DIP switch settings.

This Sigma F+E 2.0 AC/DC variant offers an auxiliary voltage connection. If the auxiliary voltage fails in the event of a fault, the LED display can be operated with capacitor support for up to 8 hours.

Product features

  • Short-circuit and earth fault detection from just three single-phase current sensors
  • Phase-selective fault display
  • Short circuit: load-dependent self-adjustment or fixed response values
  • Single and double flashing mode for beam and ring nets
  • With auxiliary voltage connection and capacitor storage as AC/DC variant

Setting via DIP switch behind front panel

Bright, phase-selective short-circuit LED display

Test/reset button

Your added value

  • No false excitation due to higher harmonics
  • Clearly visible LED error display
  • Detection of high-resistance earth faults
  • Retrofit ready for earth and short-circuit indicators with monitoring/control and fault direction function

Connection of telecommunication contacts

Push-in clamps for quick installation

Technical data

Sigma R+D 2.0
Short-circuit indicator
Earth fault indicator
Earth fault location method Earth short circuit
I>> Response valuesShort-circuit current 200, 300, 400, 600, 800, 1,000, 2,000 A Self-adjustment depending on the operating current (IB):IB < 100 A → I>> = 400 A, IB > 100 A → I>> = 4 x IB
tI>> Response delay 40 ms, 80 ms
IE> Response valuesEarth fault current 20, 40, 60, 80, 100, 120, 160 A
tIE> Response delay 80, 160 ms
Response tolerance ±5 % (0 – 630 A)±10 % (>630 A)
Display 3 red LEDs: Short circuit: 2- or 3-pole (L1, L2, L3)Earth fault: 1-pole
Remote signaling / communication 2 potential-free relay contacts
Remote signaling contact Potential-free continuous or wiping contact (1 s)Contact rating: 230 V AC / 1 A / 62.5 VA max.;220 V DC / 1 A / 60 W max.
Reset
  • Via push-button
  • Remote reset
  • Automatic time reset: 1, 2, 4 or 8 h
Supply
Converter power supply
External auxiliary voltage AC/DC variant: 24 – 230 V AC/DC
Internal supply Long-life lithium cell, service life ≥20 years, > 900 h total flashing timeAC/DC variant: back-up capacitor, max. 8 h
Housing Polycarbonate, IP40
Temperature range -30 °C to +70 °C

All important documents for the device

Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.

Matching articles

PERFECT MATCH

Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.

Equipment set

Other short-circuit and earth fault indicators

Sigma R+D 3 2.0

Sigma D+

Sigma D++

Sigma DM