ComPass A 2.0
Short-circuit and earth fault indicator with current monitoring
The ComPass A 2.0 is suitable for use in central substations with telecontrol connection of electrical energy distribution in the medium-voltage grid. Fault values and pre-fault values are recorded and provided with a time stamp. In addition to the short-circuit and earth fault display, the ComPass A 2.0 measures the temperature, e.g. of the transformer or the station with a PT100. The collected information, measured values and the associated limit values are made available for transmission to the control room. Short-circuits and earth faults are also shown phase-selectively on the OLED display.
Product features
- Short-circuit and earth fault indicators for all medium-voltage networks
- Short-circuit and earth fault detection from just three single-phase current sensors
- LED and OLED display: for good visibility
- Two earth fault location methods
- Highly accurate current measurement up to 0.5 %
- High-precision monitoring of the variables current (I), temperature (T) and frequency (f)
- PT100 temperature sensor for monitoring operating equipment
- Limit value monitoring: I, T
- ComPass Explorer software: Commissioning and parameterization via front USB port
- Pulse localization for RESPE network

OLED display for good readability
Display of measured values and configuration via the display
Rocker switch
Mini-USB port for easy parameterization and commissioning
Your added value
- Fast commissioning and parameterization
- One indicator for all networks
- Retrofit ready for earth and short-circuit indicators with
monitoring/control and fault direction function
Reverse polarity protected plug-in terminals for quick and easy installation
Modbus interface
PT100
Earthing terminals
Current sensor connection
Binary inputs
Technical data
ComPass A 2.0 | |
---|---|
Short-circuit indicator | ✅ |
Earth fault indicator | ✅ |
Earth fault location method | Earth short circuit, pulse detection |
Measured values / display |
|
I>> Response values Short-circuit current | 10 – 2,000 A, self-adjustment (200 – 2,000 A) |
tI>> Response delay | 20 ms – 60 s |
IE> Response values earth fault current | 10 – 1.000 A |
tIE> Response delay | 40 ms – 60 s |
ΔIE> Response values for pulse detection (clock stroke) | 1 – 200 A |
Limit value monitoring | |
I> Overcurrent | 5 – 1,500 A; tI> Response delay: 40 ms – 60 s |
T< / T<< / T> / T>> Temperature | -40 °C to +85 °C |
Measuring accuracy phase currents | ≤0.5 % / 0.5 A closed sensor type, ≤1 % / 0.5 A divisible sensor type |
Display | LED status display (multicolor) OLED display (multilingual) |
Remote signaling / communication | 4 potential-free, freely programmable relay contacts RS485 / Modbus interface |
Parameterization | USB connection with ComPass Explorer software |
Telecommunication contact | 4 permanent or wiping contacts, bistable, NC or NO contact Contact rating: 230 V AC/1 A/62.5 VA max.; 220 V DC/1 A/60 W max. |
Binary inputs | 2, potential-free, 1 s < t < 5 s, freely programmable |
Reset |
|
Supply | |
External auxiliary voltage | 24 V – 230 V AC / DC (±10 %) |
Internal power supply | Long-life lithium cell, >1,000 h total flashing time of the LED, >1,000 display activations |
Housing | Polycarbonate, IP50 |
Temperature range | -30 °C to +70 °C |
All important documents for the device
Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.
Matching articles
PERFECT MATCH
Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.
Product finder
Find the right Horstmann product for your application quickly and easily.
Other short-circuit and earth fault indicators
ComPass B
- Highly accurate monitoring
- Detection of earth faults and short circuits for all networks
- Remote signaling via RS485 / Modbus interface
ComPass B 2.0
- Highly accurate monitoring
- Detection of earth faults and short circuits for all networks
- Error direction display
ComPass Bs 2.0
- Fault direction indicator with monitoring
- Detection of earth faults and short circuits for all networks
- Switching ComPass Bs 2.0 for controlling a switch-disconnector or circuit-breaker remotely