ComPass A 2.0

Short-circuit and earth fault indicator with current monitoring

The ComPass A 2.0 is suitable for use in central substations with telecontrol connection of electrical energy distribution in the medium-voltage grid. Fault values and pre-fault values are recorded and provided with a time stamp. In addition to the short-circuit and earth fault display, the ComPass A 2.0 measures the temperature, e.g. of the transformer or the station with a PT100. The collected information, measured values and the associated limit values are made available for transmission to the control room. Short-circuits and earth faults are also shown phase-selectively on the OLED display.

Product features

  • Short-circuit and earth fault indicators for all medium-voltage networks
  • Short-circuit and earth fault detection from just three single-phase current sensors
  • LED and OLED display: for good visibility
  • Two earth fault location methods
  • Highly accurate current measurement up to 0.5 %
  • High-precision monitoring of the variables current (I), temperature (T) and frequency (f)
  • PT100 temperature sensor for monitoring operating equipment
  • Limit value monitoring: I, T
  • ComPass Explorer software: Commissioning and parameterization via front USB port
  • Pulse localization for RESPE network

OLED display for good readability

Display of measured values and configuration via the display

Rocker switch

Mini-USB port for easy parameterization and commissioning

Your added value

  • Fast commissioning and parameterization
  • One indicator for all networks
  • Retrofit ready for earth and short-circuit indicators with
    monitoring/control and fault direction function

Reverse polarity protected plug-in terminals for quick and easy installation

Modbus interface

PT100

Earthing terminals

Current sensor connection

Binary inputs

Technical data

ComPass A 2.0
Short-circuit indicator
Earth fault indicator
Earth fault location method Earth short circuit, pulse detection
Measured values / display
  • Operating current, I 1,2,3 Ø value adjustable (1 – 60min), I max. 24 h / 7 days / 365 days, drag indicator function I max. LR T min. LR, Tmax. LR Mains frequency f
  • Temperature T
I>> Response values Short-circuit current 10 – 2,000 A, self-adjustment (200 – 2,000 A)
tI>> Response delay 20 ms – 60 s
IE> Response values earth fault current 10 – 1.000 A
tIE> Response delay 40 ms – 60 s
ΔIE> Response values for pulse detection (clock stroke) 1 – 200 A
Limit value monitoring
I> Overcurrent 5 – 1,500 A; tI> Response delay: 40 ms – 60 s
T< / T<< / T> / T>> Temperature -40 °C to +85 °C
Measuring accuracy phase currents ≤0.5 % / 0.5 A closed sensor type, ≤1 % / 0.5 A divisible sensor type
Display LED status display (multicolor)
OLED display (multilingual)
Remote signaling / communication 4 potential-free, freely programmable relay contacts
RS485 / Modbus interface
Parameterization USB connection with ComPass Explorer software
Telecommunication contact 4 permanent or wiping contacts, bistable, NC or NO contact
Contact rating: 230 V AC/1 A/62.5 VA max.;
220 V DC/1 A/60 W max.
Binary inputs 2, potential-free, 1 s < t < 5 s, freely programmable
Reset
  • Via rocker switch
  • Remote reset
  • Automatic time reset: 1 min – 24 h
  • Via RS485/Modbus interface
  • Power recovery
  • Auxiliary voltage recovery
  • ComPass Explorer Software
Supply
External auxiliary voltage 24 V – 230 V AC / DC (±10 %)
Internal power supply Long-life lithium cell, >1,000 h total flashing time of the LED,
>1,000 display activations
Housing Polycarbonate, IP50
Temperature range -30 °C to +70 °C

All important documents for the device

Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.

Matching articles

PERFECT MATCH

Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.

Equipment set

Product finder

Find the right Horstmann product for your application quickly and easily.

Other short-circuit and earth fault indicators

ComPass B

ComPass B 2.0

ComPass Bs 2.0