Sigma D⁺⁺⁺
Error direction indicator
The Sigma D++ is a combined short-circuit direction and earth fault direction indicator for medium-voltage networks. The current is measured via phase current sensors. The measuring voltage can be tapped via integrated voltage test systems (Wega series), via HR / LRM interfaces or probes with capacitive decoupling. Additional earth fault detection methods are available in the Sigma D++ for the various neutral point treatments (extinguished and isolated systems).
The earth fault wiper method only requires three phase current sensors, but requires the auxiliary power supply to be connected. A summation current sensor can be connected as an option. No auxiliary voltage is required for all other fault location methods if the operating current >is 5 A.
Product features
- Transformer-powered short-circuit direction indicator and earth fault direction indicator for all networks and neutral point treatments
- Requires only three phase current sensors for all earth fault location methods
- Earth fault detection with up to five different earth fault detection methods, can also be combined
- Independent, fully automatic voltage calibration
- Simple and flexible parameterization via DIP switch or USB
- Event memory for error evaluation
- LED status display, multicolor
- Remote signaling via freely programmable signal relays
- Sigma Explorer software: Commissioning, parameterization and reading out the fault memory via the front USB port
- With wide-range power supply 24 V to 230 V AC/DC
Phase-selective short-circuit and earth fault display
Clear error direction display
Differentiation between short-circuit and earth fault
Status indicator LED
Your added value
- Immediate error direction detection
- Fast commissioning and parameterization
- On-site monitoring with USB and notebook
Reverse polarity protected plug-in terminals for quick and easy installation
Connection for voltage coupling (Wega)
Technical data
Sigma D++ | |
---|---|
Short-circuit indicator | ✅ |
Earth fault indicator | ✅ |
Earth fault location method | Continuous earth fault, earth short circuit, cos φ and sin φ methods, pulse detection, earth fault wiper |
I>> Response values Short-circuit current |
|
tI>> Response delay | DIP: 40, 80 ms; SW: 40 ms – 60 s |
IES> / IES>> Earth fault current response values | DIP: off, 20, 40, 60, 80, 100, 120, 160 A; SW: 10 – 1,000 A (1 A steps) |
tIE> Response delay | DIP: 80, 160 ms; SW: 40 ms – 60 s |
IET> Response values earth fault wiper method | 10 – 500 A |
IEP> Response values Active residual current cos φ | 2 – 200 A |
IEQ> Response values Reactive current sin φ | 2 – 200 A |
tIEP> / tIEQ>Response delay | 40 ms – 60 s |
ΔIE> Response values for pulse detection (clock stroke) | 1 – 100 A |
Measuring accuracy phase currents | 3 % (0 – 630 A, resolution 1 A)5 % (630 – 1,500 A)10 % (1,500 – 2,000 A) |
Display |
|
Remote signaling / communication | 4 potential-free, freely programmable relay contacts |
Parameterization |
|
Remote signaling contact | 4 permanent or wiping contacts (1 s), NC or NO contact Contact rating: 230 V AC / 1 A / 62.5 VA max.;220 V DC / 1 A / 60 W max. |
Voltage calibration | Manual / Automatic |
Reset |
|
Supply | |
Converter power supply | ✅ |
External auxiliary voltage | 24 – 230 V AC/DC possible (necessary for earth fault wiper) |
Internal power supply | Long-life lithium cell; service life ≥20 years |
Total current sensor | optional |
Housing | Polycarbonate, IP40 |
Temperature range | -30 °C to +70 °C |
All important documents for the device
Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.
Matching articles
PERFECT MATCH
Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.
Other short-circuit and earth fault indicators
Sigma D
- Phase-selective short-circuit indicator with direction indicator
- Earth short-circuit monitoring with direction indication in NOSPE networks and OSPE networks with "open" rings
- Current measurement via phase current sensors.
Sigma D+
- Phase-selective short-circuit indicator with direction indicator
- Earth shot location method for all neutral point treatments in MV networks
- Earth fault detection with 5 detection methods with total current sensor
Sigma DM
- OLED display for good readability in all lighting conditions
- Display of measured values and configuration via the display
- Quick and easy to operate rocker switch
Sigma L series
- Clear error type display with differentiated LED display
- Flexible adjustment of the triggering criteria for short-circuit trips
- Transmission of data via the 868 MHz radio frequency with LoRaWAN protocol