BO-A 2.0
Voltage detector for railway overhead contact lines
The BO-A 2.0 is a voltage detector for medium voltage railway overhead contact lines. It is designed to detect the absence or presence of voltage during maintenance work, for example. The voltage detector BO-A 2.0 is developed for 16.7 Hz, 50 Hz, and 60 Hz networks. If the voltage detector BO-A 2.0 is used in a network with a deviating frequency, a visual and audible signal is activated. In this case, the network situation must be verified. The BO-A 2.0 is designed according to IEC 61243-1 resp. VDE 0681-6,
depending on the version. The voltage detector is ready for the worldwide market.
According to the German accident prevention standard DGUV Regulation 3 (Table 1c), the device is subject to maintenance tests with minimum intervals of at least 6 years.
Product features
- Use: In dry and wet conditions
- Ready: green LED (after successful self-test)
“Voltage present”: red LED and acoustic signal
“Voltage not present”: green LED and no audible signal - Period of “Stand-by state”: 65 s ±15 s
(automatic self-activation available as an option) - Type of indication: According to group III IEC 61243-1
Rated voltage / rated frequency: 15 kV / 16.7 Hz, 25 kV/ 50 Hz or 25 kV/ 60 Hz (others on request) - Operating temperature: -25 to +70 °C, climate class N and W
Your added value
- Light weight and comfortable bag – Easy handling and transportation
- Integrated self-test – maximum safety
- Plug-in and telescopic system – Quick and easy to use
- Bright LEDs and loud acoustic signals – good perception in all conditions
- Shockproof and no battery replacement – Maintenance-free (> 6 years)
- Automatic frequency detection – Increased user safety
Acoustic detector
On/off button
Red LED
"Voltage present"
Green LED
"No voltage present"
and standby mode
Technical data
BO-A 2.0 | |
---|---|
Application | In dry and wet conditions |
Display |
|
Period of “Stand-by state” | 65 s ±15 s |
Type of indication | According to group III of IEC 61243-1 |
Nominal voltage / nominal frequency |
|
Properties of the insulating rod | Passed test as insulating element for leakage current at 1.2 x Vr for 1 min |
Power supply | Lithium cells 6 years with approx. 10 standby cycles / day and 230 days / year |
Transport length | <1,111 mm |
Minimum length of insulating element | >520 mm |
Operating temperature | -25 °C to +70 °C, climate class N and W |
Versions
Nominal voltage [kV] Nominal frequency [Hz] |
Total length a [mm] ±50 mm |
Insertion depth b [mm] | Handling | Version | Order no. |
---|---|---|---|---|---|
15 kV / 16.7 Hz | max. 5,400 | 1.790 | Telescopic rod / plug-in adapter | VDE version DB approval |
50-1510-202 |
15 kV / 16.7 Hz | max. 5,400 | 1.790 | Telescopic rod / plug-in adapter | IEC version Automatic self-closing |
50-1512-002 |
15 kV / 16.7 Hz | 4.700 | 1.790 | Insulating rods (pluggable) | VDE version DB approval |
50-1510-002 |
11 kV / 16.7 Hz | 4.700 | 1.790 | Insulating bars (pluggable) | VDE version Automatic self-closing |
50-1510-301 |
All important documents for the device
Do you need additional information about our device? In our download area you will find all relevant documents such as brochures and product catalogs, technical reports, operating instructions and dimensional drawings (login required). Simply click on the download area to obtain the documents you require.
Matching articles
PERFECT MATCH
Here you will find the matching equipment set and accessories for this item. All components are technically matched to each other and guarantee optimum functionality. For customer-specific requirements and individual offers, please contact our sales department.
Equipment set
- 1 BO-A 2.0 voltage detector
Accessories
- Storage bag
Other voltage detector
BO-A AC/DC
- DC voltage detector for overhead lines of electric railways
- Simple plug-in and telescopic system
- Low weight - easy to transport